![Emerson Powerdrive F300 Reference Manual Download Page 153](http://html.mh-extra.com/html/emerson/powerdrive-f300/powerdrive-f300_reference-manual_102547153.webp)
Parameter
09.020
Logic Function 2 Destination
Short description
Defines the output destination of logic function 2
Mode
Open
‑
Loop
Minimum
0.000
Maximum
59.999
Default
0.000
Units
Type
16 Bit User Save
Update Rate
Drive reset read
Display Format
Standard
Decimal Places
3
Coding
RW, DE, PT, BU
Logic Function 2 Destination
(09.020) defines the output destination of logic function 2.
Parameter
09.021
Motorised Pot Mode
Short description
Defines the motorised pot mode
Mode
Open
‑
Loop
Minimum
0
Maximum
4
Default
0
Units
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW
Motorised Pot Mode
(09.021) defines the mode of operation as given in the table below.
Motorised Pot Mode
(09.021)
Motorised Pot Output
(09.003)
Motorised Pot Up
(09.026) and
Motorised Pot Down
(09.027) active
0
Reset to zero at power-up
Always
1
Set to power-down value at power-up
Always
2
Reset to zero at power-up
When
Drive Active
(10.002) = 1
3
Set to power-down value at power-up
When
Drive Active
(10.002) = 1
4
Reset to zero at power-up and when
Drive Active
(10.002) = 0
When
Drive Active
(10.002) = 1
Parameter
09.022
Motorised Pot Bipolar Select
Short description
Set to enable bipolar operation of the motorised pot
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit User Save
Update Rate
4ms read
Display Format
Standard
Decimal Places
0
Coding
RW
If
Motorised Pot Bipolar Select
(09.022) = 0 then
Motorised Pot Output
(09.003) is limited in the range 0.00% to 100.00%, otherwise it is allowed to
change in the range from -100.00% to 100.00%.
Parameter
09.023
Motorised Pot Rate
Short description
Defines the rate of change of the motorised pot output
Mode
Open
‑
Loop
Minimum
0
Maximum
250
Default
20
Units
s
Type
8 Bit User Save
Update Rate
Background
Display Format
Standard
Decimal Places
0
Coding
RW, BU
The rate of change of
Motorised Pot Output
(09.003) is defined by
Motorised Pot Rate
(09.023) which gives the time to change from 0 to 100%. The
time to change from -100% to 100% is
Motorised Pot Rate
(09.023) x 2.
Parameter
09.024
Motorised Pot Scaling
Short description
Mode
Open
‑
Loop
Minimum
0.000
Maximum
4.000
Default
1.000
Units
Type
16 Bit User Save
Update Rate
4ms read
Display Format
Standard
Decimal Places
3
Coding
RW
Motorised Pot Scaling
(09.024) introduces a scaling factor at the output of the motorised pot before the output is routed to the destination. If
Motorised Pot Scaling
(09.024)
Motorised Pot Scaling
(09.024) > 1.000 the output will exceed the range of the destination parameter, and so the
destination parameter will be at its maximum or minimum before the output of the motorised pot reaches the limits of its range.
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
153
Summary of Contents for Powerdrive F300
Page 1: ...Parameter Reference Guide Powerdrive F300 Open Loop Mode Issue 01 15 00 ...
Page 21: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 21 ...
Page 112: ...112 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Page 144: ...144 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Page 231: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 231 ...
Page 232: ...232 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...