102
Image has detected an array bounds violation and
prevented its access.
103
Image has attempted to convert a data type to or from an
unknown data type, has failed and has shut itself down.
104
Image has attempted to use an unknown user service
function.
200
User program has invoked a “divide” service with a
denominator of zero. (Note that this is raised by the
downloaded image and has therefore been given a
distinct error code despite being the same fundamental
problem as sub-trip 1.)
201
Parameter access is not supported. An attempt to read
database other than the host drive.
202
Parameter does not exist. Database was host drive but
the specified parameter does not exist.
203
Parameter is read-only.
204
Parameter is write-only.
205
Unknown parameter error.
206
Invalid bit present in parameter. The parameter does not
contain the specified bit.
207
Parameter format lookup failed. Failed to get parameter
information data.
208
An over-range write has been attempted.
The following table gives the differences when compared to the derivative product image.
Sub-trip
Difference
40, 41
Onboard User Program: Enable (11.047)
is reset to zero when the trip is initiated.
51
Not applicable as core menu customisation not allowed
6x
Not applicable as option module restrictions not allowed
7x
Not applicable as option module restrictions not allowed
100
Image has detected and prevented attempted pointer access outside of the IEC task’s heap area.
101
Image has detected and prevented misaligned pointer usage.
102
Image has detected an array bounds violation and prevented its access.
103
Image has attempted to convert a data type to or from an unknown data type, has failed and has shut itself
down.
104
Image has attempted to use an unknown user service function.
200
User program has invoked a “divide” service with a denominator of zero. (Note that this is raised by the
downloaded image and has therefore been given a distinct error code despite being the same fundamental
problem as sub-trip 1.)
Trip
User Save
Value
36
Short description
This trip indicates that an error has been detected in the user save parameters saved in non-volatile memory. For example, fillowing a user save command, if the
power to the drive was removed when the user parameters were being saved.
Recommended actions:
Perform a user save in Pr
mm.000
to ensure that the trip doesn't occur the next time the drive is powered up.
Ensure that the drive has enough time to complete the save before removing the power to the drive.
334
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
Summary of Contents for Powerdrive F300
Page 1: ...Parameter Reference Guide Powerdrive F300 Open Loop Mode Issue 01 15 00 ...
Page 21: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 21 ...
Page 112: ...112 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Page 144: ...144 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Page 231: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 231 ...
Page 232: ...232 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...