Parameter
06.052
Motor Pre-heat Current Magnitude
Short description
Defines the current in the motor when the state machine is in the stop state
Mode
Open
‑
Loop
Minimum
0
Maximum
100
Default
0
Units
%
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW
See
Hold Zero Speed
(06.008).
Parameter
06.053
Sleep / Wake Threshold
Short description
Defines the threshold used for enabling the sleep/wake function
Mode
Open
‑
Loop
Minimum
−VM_SPEED_FREQ_REF_UNIPOLAR Maximum
VM_SPEED_FREQ_REF_UNIPOLAR
Default
0.0
Units
Type
32 Bit User Save
Update Rate
Display Format
Standard
Decimal Places
1
Coding
RW, VM
The diagram below shows the sleep mode detection system. If Fire mode active = 1,
Reference Selected Indicator
(01.049) = 4, the Run excluding sleep
= 0 or
Sleep / Wake Threshold
(06.053) = 0 then the sleep mode system is disabled, and so
Sleep Required
(06.056) and
Sleep Active
(06.057) are held
at zero.
The sleep mode system will stop the motor if |
Reference Selected
(01.001)| <
Sleep / Wake Threshold
(06.053) for a time equal to
Sleep Time
(06.054)
and restart the motor if |
Reference Selected
(01.001)| ≥
Sleep / Wake Threshold
(06.053) for a time equal to
Wake Time
(06.055). If
Bipolar Reference Enable
(01.010) = 0 (i.e. unipolar mode is being used) then negative values of
Reference Selected
(01.001) are treated as zero. It is
possible for the PID controller (Menu 14) to hold off sleep mode by setting
PID1 Pre-sleep Boost Level
(14.028) to 1.
Parameter
06.054
Sleep Time
Short description
Defines the time that the drive will stop the motor if the sleep function is active
Mode
Open
‑
Loop
Minimum
0.0
Maximum
250.0
Default
10.0
Units
s
Type
16 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
1
Coding
RW
See
Sleep / Wake Threshold
(06.053).
Parameter
06.055
Wake Time
Short description
Defines the time that the drive will restartthe motor if the wake function is active
Mode
Open
‑
Loop
Minimum
0.0
Maximum
250.0
Default
10.0
Units
s
Type
16 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
1
Coding
RW
96
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
Summary of Contents for Powerdrive F300
Page 1: ...Parameter Reference Guide Powerdrive F300 Open Loop Mode Issue 01 15 00 ...
Page 21: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 21 ...
Page 112: ...112 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Page 144: ...144 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Page 231: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 231 ...
Page 232: ...232 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...