A
1S
= A
1O
x
Analog Input 1 Scaling
(07.008)
A
1S
is the value after the scaling and the offset have been applied and is limited between -100.00% and 100.00%
If
Analog Input 1 Invert
(07.009) = 0 then A
1I
= A
1S
otherwise A
1I
= -A
1S
A
1I
is the value after the invert, scaling and offset have been applied and is the final value that is routed to the destination defined
by
Analog Input 1 Destination
(07.010).
Parameter
07.009
Analog Input 1 Invert
Short description
Inverts the signal for analog input 1
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW
See
Analog Input 1 Scaling
(07.008).
Parameter
07.010
Analog Input 1 Destination
Short description
Defines the output parameter for analog input 1
Mode
Open
‑
Loop
Minimum
0.000
Maximum
59.999
Default
1.036
Units
Type
16 Bit User Save
Update Rate
Drive reset read
Display Format
Standard
Decimal Places
3
Coding
RW, DE, PT, BU
See
Analog Input 1 Scaling
(07.008).
Parameter
07.011
Analog Input 2 Mode
Short description
Defines the mode for analog input 2
Mode
Open
‑
Loop
Minimum
-4
Maximum
9
Default
6
Units
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW, TE
Value
Text
Description
‑
4
4-20mA Low
4-20mA low value on current loss
‑
3
20-4mA Low
20-4mA low value on current loss
‑
2
4-20mA Hold
4-20mA hold at level before loss on current loss
‑
1
20-4mA Hold
20-4mA hold at level before loss on current loss
0
0-20mA
0-20mA
1
20-0mA
20-0mA
2
4-20mA Trip
4-20mA trip on current loss
3
20-4mA Trip
20-4mA trip on current loss
4
4-20mA
4-20mA no action on loss
5
20-4mA
20-4mA no action on loss
6
Volt
Voltage
7
Therm Short Cct
Temperature measurement input with short circuit detection
8
Thermistor
Temperature measurement without short circuit detection
9
Therm No Trip
Temperature measurement input with no trips
See
Analog Input 1 Mode
(07.007).
Parameter
07.012
Analog Input 2 Scaling
Short description
Defines the scaling factor for analog input 2
Mode
Open
‑
Loop
Minimum
0.000
Maximum
10.000
Default
1.000
Units
Type
16 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
3
Coding
RW
The scaling, offset and invert functions for analog input 2 are defined in the same way as for analog input 1. See
Analog Input 1 Scaling
(07.008).
116
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
Summary of Contents for Powerdrive F300
Page 1: ...Parameter Reference Guide Powerdrive F300 Open Loop Mode Issue 01 15 00 ...
Page 21: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 21 ...
Page 112: ...112 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Page 144: ...144 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Page 231: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 231 ...
Page 232: ...232 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...