Parameter
10.081
Phase Loss
Short description
Indicates that the drive has detected an input phase loss
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
Background Write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
If phase loss or imbalance is detected that would initiate a phase loss trip with sub-trip 0, i.e.
Phase Loss
.000, then
Phase Loss
(10.081) is set to one.
Either the motor will be stopped and the drive tripped or the drive will continue to operate normally until the user stops the motor and the drive trips (see
Action On Trip Detection
(10.037)). In either case
Phase Loss
(10.081) is set to one when the phase loss condition is detected and remains set until the
drive trips.
Parameter
10.101
Drive Status
Short description
Shows the present status of the drive
Mode
Open
‑
Loop
Minimum
0
Maximum
16
Default
Units
Type
8 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, TE, ND, NC, PT, BU
Value
Text
0
Inhibit
1
Ready
2
Stop
3
Scan
4
Run
5
Supply Loss
6
Deceleration
7
dc Injection
8
Position
9
Trip
10
Active
11
Off
12
Hand
13
Auto
14
Heat
15
Under Voltage
16
Phasing
Drive Status
(10.101) shows the present status of the drive. The strings from this parameter are also used by the basic keypad to provide the status
display text.
Parameter
10.102
Trip Reset Source
Short description
Indicates whether a trip in the trip log has been reset.
Mode
Open
‑
Loop
Minimum
0
Maximum
1023
Default
Units
Type
16 Bit Power Down Save
Update Rate
Write on trip
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT, BU
The bits in
Trip Reset Source
(10.102) correspond to each of the trips in the trip log (i.e. bit 0 corresponds to trip 0, bit 1 corresponds to trip 1, etc.).
When a trip occurs, bit 0 is set to one and the other bits corresponding to the trips already in the trip log are shifted left one bit. If the trip is reset then bit
0 is set back to zero, otherwise if a higher priority trip occurs bit 0 is shifted left by one bit. The result is that each of the bits in
Trip Reset Source
(10.102) show whether trips in the trip log were reset or moved up the trip log by a higher priority trip.
Parameter
10.103
Trip Time Identifier
Short description
Shows time in milliseconds since the drive powered up when a trip occurred
Mode
Open
‑
Loop
Minimum
-2147483648
Maximum
2147483647
Default
Units
ms
Type
32 Bit Volatile
Update Rate
Write on trip
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
When a trip occurs the time in milliseconds since the drive powered up is stored in
Trip Time Identifier
(10.103). The time rolls-over when it reaches
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
191
Summary of Contents for Powerdrive F300
Page 1: ...Parameter Reference Guide Powerdrive F300 Open Loop Mode Issue 01 15 00 ...
Page 21: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 21 ...
Page 112: ...112 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Page 144: ...144 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Page 231: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 231 ...
Page 232: ...232 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...