RSTi-OM User Manual
Section 9
GFK-3212A
Jun 2021
PROFINET IO Reference Information
92
Port Status
Displays the port status:
Inactive = The port is in an active state. Typically, this
indicates that the device is either not attached or not
detected.
Initializing = The port is in the process of initializing.
Operational = The port is operational and if in IO-Link
mode, communications to the IO-Link device have been
established.
PDI Valid = The PDI data is now valid.
Fault = The port has detected a fault and is unable to re-
establish communications.
IO-Link State
Operate - Port is functioning correctly in IO-Link mode but
has not received valid PDI data. This may also display during
a data storage upload or download.
Init - The port is attempting initialization.
Reset - One of the following conditions exists:
The Port Mode configuration is set to Reset.
The Port Mode configuration is set to DigitalIn or
DigitalOut.
DS - Wrong Sensor - Hardware failure (IO-Link LED also
flashes red) because there is Data Storage on this port,
which does not reflect the attached device.
DV - Wrong Sensor - Hardware failure (IO-Link LED also
flashes red) because Device Validation is configured for this
port and the wrong device is attached.
DS - Wrong Size - Hardware failure (IO-Link LED also flashes
red) because the size of the configuration on the device
does not match the size of the configuration stored on the
port.
Comm Lost - Temporary state after a device is disconnected
and before the port is re-initialized.
Pre-operate - Temporary status displayed when the device:
It starting up after connection or power-up.
Uploading or downloading automatic data storage.
Device Vendor Name
Displays the Device Vendor Name as stored in ISDU Index
16.
Device Product Name
Displays the device product name as stored in ISDU Index
18.
Device Serial Number
Displays the device serial number as stored in ISDU Index
21.
Device Hardware Version
Displays the device hardware version as stored in ISDU
Index 22.
Device Firmware Version
Displays the device firmware version as stored in ISDU Index
23.
Device IO-Link Version
The supported device IO-Link version is stored in ISDU Index
0.
Actual Cycle Time
This is the actual, or current, a cycle time of the IO-Link
connection to the device.
Device Minimum Cycle Time This is the minimum, or fastest, cycle time supported by the
connected IO-Link device.
Configured Minimum Cycle
Time
Configured in the Configuration | IO-Link page, this is the
minimum cycle time the IO-Link Master will allow the port to
operate at. The Actual Cycle Time, which is negotiated
between the IO-Link Master and the device, will be at least as
long as the greater of the Configured Minimum Cycle Time
and the Device Minimum Cycle Time.
Data Storage Capable
Displays whether the IO-Link device on a port supports the
data storage feature. Not all IO-Link devices support the data
storage feature.