RSTi-OM User Manual
Section 6
GFK-3212A
Jun 2021
IO-Link Master Port Configuration
63
Modbus/TCP Settings Page
Clear Event Code After Hold
Time
Default
: True
If enabled, the IO-Link Master clears any event code reported in the PDI
data block after the Event Active Hold Time.
Values are:
True (enable check box) = clear event code after hold time
False = do not clear event code after the hold time
Active Event Hold Time
Default
: 1000 ms
If Clear Event Code After Hold Time is enabled, the time period an
event code is reported in the PDI block before it is cleared.
Valid range: 1-65535
Valid Units are:
ms (milliseconds)
sec (seconds)
min (minutes)
hours
days
Event Hold Time Units
Valid Units:
ms (milliseconds)
sec (seconds)
min (minutes)
hours
days
Clear Event Hold Time
Default
: 500 ms
Once an event code has been cleared, the time an event code stays
cleared in the PDI block before another event code can be reported.
Valid range: 1-65535
Valid Units:
ms (milliseconds)
sec (seconds)
min (minutes)
hours
days
Event Clear Time Units
Valid Units:
ms (milliseconds)
sec (seconds)
min (minutes)
hours
days
Include Digital Output(s) in
PDO Data Block
Default
: False
If enabled, the IO-Link Master expects the digital output settings to
be included in the PDO data block.
False
–
The digital pin setting(s) are not included in the PDO data
block
True (enable check box)
–
The digital pin setting(s) are included in the
PDO data block
Transfer Mode Settings
Slave Mode Device ID
Default
: 1
The Modbus Device ID was used to access this IO-Link port.
Range: 1-247
PDI Receive Mode(s)
Default
: Slave
Determines which PDI Receive (To PLC) Modes are enabled. The
selectable modes are:
Slave
Master
PDO Transmit Mode
Default
: Slave
Selectable Modes are:
Disabled
Slave
Master
Modbus Master PLC IP
Address
The IP address of the Modbus slave.
Modbus Master PLC Device ID
(1-247)
(Default: 1)
The Modbus Device ID was used to access the slave.
Modbus Master PLC PDI Data
Address (base 1)
(1-65535)
(Default: 1)
The address of the slave’s PDI (determined by the slave).
Modbus Master PLC Max
Update Rate (0-10000)
(Default: 0)
How often to write PDI to the slave.
Modbus Master PLC PDO Data
Address (base 1) (1-65535)
(Default:1)
The address of the slave’s PDO (determined by the slave).
Modbus Master PLC Poll Rate
(40- 65535)
(Default: 40)
How often to read PDO from the slave.