RSTi-OM User Manual
Section 6
GFK-3212A
Jun 2021
IO-Link Master Port Configuration
55
Figure 41: IO-Link Settings
Note: You can click each EDIT button and open all ports to quickly configure port parameters.
1.Make appropriate selections for the device that you connected to that port.
Make sure you select the DigitalIn option for a digital input device and the DigitalOut option for a
digital output device for the Port Mode.
The IOLM negotiates the Minimum Cycle Time so it is not necessary to set a cycle time unless you
need a specific cycle time.
You can use the help system if you require definitions or values for the options or refer to the
following subsection (
Note: Do not enable Automatic Download and then attempt device configuration as Automatic
Download changes the settings back to what is stored on the IOLM. Data Storage, Device Validation,
and Data Validation are discussed in Section Section 9:
1.
Click the SAVE button for each port.
2.
Return to the IO-Link Diagnostics page to verify that your changes have taken effect.