RSTi-OM User Manual
Section 6
GFK-3212A
Jun 2021
IO-Link Master Port Configuration
59
6.3
PROFINET IO Settings Configuration Page
The following table provides information about the Configuration| PROFINET IO page options.
You can refer to Section 3.5,
for PROFINET IO configuration procedures. You must have Administrator or Operator privileges to
change any settings on this page.
Figure 42: Configuration Page
PROFINET IO Settings Page
PROFINET IO Device Name
The PROFINET IO Device Name is the same as the name later used
to configure PROFINET IO for the IO-Link Master.
The device name must be specified according to DNS
conventions.
Restricted to a total of 240 characters (letters, digits, dash, or
period)
Parts of the name within the device name; in other words, a string
between two periods, must not exceed a maximum of 63
characters.
No special characters such as umlauts (ä, ö, etc.), brackets,
underscore, slash, blank, etc. The dash is the only permitted
special character.
The device name must not begin or end with the "-" character.
The device name must not begin with numbers.
The device name must not have the structure n.n.n.n (n = 0...999).
The device name must not begin with the character string "port-
xyz-" (x,y, z = 0...9).
IOL_CALL Function Block
Timeout (1-20)
The IOL_CALL Function Block Timeout range is 1 - 20 and the
default is 20.