Integrate the meter with the control system
t
Example: Cutoff interaction
Configuration:
•
mA Output Process Variable
=
Mass Flow Rate
•
Frequency Output Process Variable
=
Mass Flow Rate
•
AO Cutoff
=
10
g/s
•
Mass Flow Cutoff
=
15
g/s
Result: If the mass flow rate drops below 15 g/s, all outputs representing mass flow will report zero flow.
t
Example: Cutoff interaction
Configuration:
•
mA Output Process Variable
=
Mass Flow Rate
•
Frequency Output Process Variable
=
Mass Flow Rate
•
AO Cutoff
=
15
g/s
•
Mass Flow Cutoff
=
10
g/s
Result:
• If the mass flow rate drops below 15 g/s but not below 10 g/s:
− The mA output will report zero flow.
− The frequency output will report the actual flow rate.
• If the mass flow rate drops below 10 g/s, both outputs will report zero flow.
7.1.4
Configure
Added Damping
Display
Not available
ProLink II
ProLink→Configuration→Analog Output→Primary/Secondary Output→AO Added Damp
Field Communicator
Configure→Manual Setup→Inputs/Outputs→mA Output 1→mA Output Settings→PV Added Damping
Configure→Manual Setup→Inputs/Outputs→mA Output 2→mA Output Settings→PV Added Damping
Added Damping
controls the amount of damping that will be applied to the mA output. It affects the
reporting of
mA Output Process Variable
through the mA output only. It does not affect the reporting of that
process variable via any other method (e.g., the frequency output or digital communications), or the
value of the process variable used in calculations.
Note
Added Damping
is not applied if the mA output is fixed (for example, during loop testing) or if the mA output
is reporting a fault.
Added Damping
is applied while sensor simulation is active.
Procedure
Set
Added Damping
to the desired value.
The default value is 0.0 seconds.
122
Micro Motion 9739 MVD Transmitters