Transmitter operation
When the transmitter detects that the alarm condition has cleared:
• First status flag is set to
Inactive
.
• Second status flag is unchanged:
Unacknowledged
.
• (For
Fault
alarms only) Outputs return to reporting process data.
Operator action is required to change the second status flag; however, alarm acknowledgement is not
necessary.
8.5
Start and stop totalizers and inventories
Display
See Section 8.5.1 .
ProLink II
ProLink→Totalizer Control→Start
ProLink→Totalizer Control→Stop→Stop Totalizers
Field Communicator
Service Tools→Variables→Totalizer Control→All Totalizers→Start Totalizers
Service Tools→Variables→Totalizer Control→All Totalizers→Stop Totalizers
8.5.1
Start and stop totalizers and inventories using the display
Prerequisites
To start and stop the totalizers and inventories using the display, this feature must be enabled.
Procedure
• To stop all totalizers and inventories using the display:
a.
Scroll
until the word
TOTAL
appears in the lower left corner of the display.
Important
Because all totalizers are started or stopped together, it does not matter which total you use
to start or stop the totalizers.
b.
Select
.
c.
Scroll
until
STOP
appears beneath the current totalizer value.
d.
Select
.
e.
Select
again to confirm.
f.
Scroll
to
EXIT
.
• To start all totalizers and inventories using the display:
a.
Scroll
until the word
TOTAL
appears in the lower left corner of the display.
Important
Because all totalizers are started or stopped together, it does not matter which total you use
to start or stop the totalizers.
b.
Select
.
c.
Scroll
until
START
appears beneath the current totalizer value.
d.
Select
.
Configuration and Use Manual