Configure device options and preferences
Option
Description
Enabled
Operators can start and stop totalizers and
inventories from the display, if at least one
totalizer is configured as a display variable.
Disabled
(default)
Operators cannot start and stop totalizers and
inventories from the display.
2.
Ensure that at least one totalizer has been configured as a display variable.
This function is accessed from a totalizer value on the display. To ensure that the operator can
start and stop totalizers and inventories, at least one totalizer must be shown on the display.
6.2.2
Enable or disable
Totalizer Reset
from the display
Display
OFF-LINE MAINT→OFF-LINE CONFG→DISPLAY→TOTALS RESET
ProLink II
ProLink→Configuration→Display→Display Options→Display Totalizer Reset
Field Communicator
Not available
You can control whether or not the operator will be able to reset totalizers from the display.
Restrictions
•
Totalizer Reset
does not apply to inventories. Operators cannot reset inventories from the display,
even if
Totalizer Reset
is enabled.
• You cannot use the display to reset all totalizers as a group. From the display, you must reset
totalizers individually.
• If the petroleum measurement application is installed on your computer, the operator must enter
the off-line password to perform this function, even if the off-line password is not enabled.
Procedure
1.
Enable or disable
Totalizer Reset
as desired.
Option
Description
Enabled
Operators can reset a totalizer from the display,
if the appropriate totalizer is configured as a
display variable.
Disabled
(default)
Operators cannot reset totalizers from the
display.
2.
Ensure that the totalizers to be reset from the display have been configured as display variables.
104