Integrate the meter with the control system
The default value is
2.0
mA. The range is
1.0
mA to
3.6
mA.
Options for
mA Output Fault Action
and
mA Output Fault Level
Options for
mA Output Fault Action
and
mA Output Fault Level
are shown in Table 7-4.
Table 7-4
Options for
mA Output Fault Action
and
mA Output Fault Level
Code
ProLink II
Field Communica-
tor
mA Output Fault Level
mA output behavior
Upscale
Upscale
21–24 mA
Default: 22 mA
Goes to the configured fault level
Downscale
(default)
Downscale
(default)
0.0–3.6 mA
Default: 2.0 mA
Goes to the configured fault level
Internal Zero
Intrnl Zero
Not applicable
Goes to the mA output level
associated with a process variable
value of 0 (zero), as determined by
Lower Range Value
and
Upper Range
Value
settings
None
None
Not applicable
Tracks data for the assigned
process variable; no fault action
If you set
mA Output Fault Action
or
Frequency Output Fault Action
to
None
, be sure to set
Digital
Communications Fault Action
to
None
. If you do not, the output will not report actual process data,
and this may result in measurement error or unintended consequences for your process.
If you set
Digital Communications Fault Action
to
NAN
, you cannot set
mA Output Fault Action
or
Frequency Output Fault Action
to
None
. If you try to do this, the transmitter will not accept the
configuration.
7.2
Configure the frequency output
Display
OFF-LINE MAINT→OFF-LINE CONFG→IO→FO
ProLink II
ProLink→Configuration→Frequency
Field Communicator
Configure→Manual Setup→Inputs/Outputs→Frequency Output
The frequency output is used to report a process variable. The frequency output parameters control
how the process variable is reported.
124
Micro Motion 9739 MVD Transmitters