94 Appendix 1 Parameter Set
EV1000 Series General Purpose Variable Speed Drive User Manual
Group 2: Start/Brake Parameters
Para.
Name
Range
Unit Default Modification
F2.03
DC brake current at
startup
G type:
0.0~150.0
%
of drive’s rated current (max. among
phases)
P type:
0.0~130.0
%
of drive’s rated current (max. among
phases)
0.1
%
0.0
%
○
F2.04
DC brake time at
startup
0.0: disabled, 0.1~60.0s
0.1s
0.0s
○
F2.05 Acc/Dec mode
0: linear
1: S curve
2: auto
1
0
×
F2.06 S curve start time
10.0
%~
50.0
%
(Acc/Dec time)
F2.06+F2.07
≤
90
%
0.1
%
20.0
%
○
F2.07 S curve rising time
10.0
%~
80.0
%
(Acc/Dec time)
F2.06+F2.07
≤
90
%
0.1
%
60.0
%
○
F2.08 Stop mode
0: decelerate to stop
1: coast to stop
2: decelerate to stop+ DC brake
1
0
×
F2.09 Frequency threshold of
DC braking
0.00
~
60.00Hz
0.01Hz 0.00Hz
○
F2.10 DC brake delay
0.00
~
10.00s
0.01s
0.00s
○