Group 9: Enhanced Function
Para.
Name
Range
Unit
Default Modification
F9.01
Auxiliary freq. setting
method
0: No auxiliary freq.
1: Digital setting 1, adjust by
▲
and
▼
2: Digital setting 2, adjust by UP/DN
3: Digital setting 3, set by serial port
4: VCI analog setting
5: CCI analog setting
6: terminal pulse setting
7: - VCI analog setting
8: - CCI analog setting
9: - terminal pulse setting
10: VCI-5
11: CCI-5
12: PULSE-0.5×F1.03
13: Potentiometer
Note: it is invalid if it is the same with main freq.
setting method
For the setting of 4
~
12, it depends on F1.00
1 0
○
F9.02 Auxiliary reference factor 0.00
~
9.99 (only for F9.01=4
~
12)
0.01 1.00
○
F9.03 Digital auxiliary ref.
0.00
~
650.0Hz
0.01 0.00Hz
○