24 Chapter 3 Installation and Wiring
EV1000 Series General Purpose Variable Speed Drive User Manual
Category Terminals
Name
Function
Specification
VRF
+10V power
supply
P10V power supply
Power
supply
GND
GND of +10V
power supply
reference ground of analog signal and 10V
power supply
Output: +10V,
Setpoint accuracy:
±
10%
Max. output current: 100mA
Others TA/TB/TC Relay
output
TA, TB and TC can be defined as
multi-functional digital output signals. Please
refer to Section 5.8.
TA-TB: normally closed;
TA-TC: normally open
Contact capacity: 250VAC/2A
(COS
φ
=1), 250VAC/1A
(COS
φ
=0.4), 30V
DC
/1A
1
)
Analog Input Terminal Wiring
①
Terminal VCI receives analog voltage input,
the wiring diagram is as follows:
Shield layer near the drive
is grounded
VRF(+10V)
VCI
GND
PE
0
~
+10V
EV1000
●
●
●
Fig. 3-9 VCI Wiring Diagram
②
Terminal CCI receives analog signal. Select
current or voltage signal by setting jumper. Refer
to the figure below:
PV Series
···
CCI current
I
V
···
CCI voltage
I
V
CN10
Shield near the drive is
connected to the PE
VRF(+10V)
CCI
GND
PE
0
~
+10V
or 0/4
~
20mA
●
●
●
●
Fig. 3-10 CCI Wiring Diagram
2
)
Analog Output Terminal Wiring
If the analog output terminal AO1 and AO2 are
connected with analog meter, it can measure
many parameters. The jumpers for AO1 and AO2
are CN16 and CN17.
analog current
output
AO1
:
CN16
;
AO2
:
CN17
AO1
AO2
GND
···
0/4-20mA
0/2-10V
analog
meter
···
anlog voltage
output
0/4-20mA
0/2-10V
PV Series
●
●
●
Fig. 3-11 Analog Output Terminal Wiring
Hint:
1. When using analog input, you should install
capacitor-filter or common-mode inductor between
VCI and GND, or between CCI and GND.
2. Analog I/O signals are sensible to interference,
ensure to use shielded cable and ground it properly.
The cable length should be as short as possible.
3
)
Serial Communication Port Connection
The drive can be connected to the host with
RS485 port directly.
Fig. 3-9 shows the connection of the drive with
the host with RS232 port.
Fig. 3-13 shows the connection of the drive to
PROFIBUS system via TDS-PA01 PROFIBUS
adapter.
Using above wiring method, you can build a
“single-master single slave” system or a
“single-master multi-slaves” system. The drives in
the network can be monitored, and be controlled
remotely and automatically in real time by using a
PC or PLC controller. Thus more complicated
operation control can be realized.