Chapter 5 Parameters 79
EV1000 Series General Purpose Variable Speed Drive User Manual
Thou. Hun. Ten One
Action for communication fault
0: Alarm and coast to stop
1: No alarm, continue operation
2: No alarm, stop
(only in serial port control mode)
3: No alarm, stop ( all control modes)
Reserved
Action for EEPROM fault
0: Alarm and coast to stop
1: No alarm, continue operation
Reserved
Fig. 5-74 Protective Action Mode 1 Setting
FL.13 defines the action mode for undervoltage,
auto reset interval fault lockup and output phase
loss.
Thou. Hun. Ten One
Indication for under volt fault
-
0: No indication
1: Indicate the fault
Indication for auto reset fault
0: No indication
1: Indicate the fault
Fault lock -up
0: Disable
1: Enable (no fault indication)
2: Enable (indicate the fault)
Phase-loss protection
0: Input&output phase failure protect
1: No input phase failure protect
2: No output phase failure protect
3: No phase loss protect
Fig. 5-74 Protective Action Mode 2 Setting
Attention
!
Please be careful when using
FL.12 and FL.13, otherwise human injure or
material loss may occur.
FL.14 Fault type of the
first time
Range: 0
~
24
【
0
】
FL.15 Fault type of the
second time
Range: 0
~
24
【
0
】
FL.16 Fault type of the
third time (latest)
Range: 0
~
24
【
0
】
FL.17 Bus voltage at the
last fault
Range: 0
~
999V
【
0V
】
FL.18 Output current at
the last fault
Range:0
~
999.9A
【
0.0A
】
FL.19 Freq. at the last
fault
Range:0.00~650.00Hz
【
0.00Hz
】
EV1000 has 24 kinds of alarms. It can memorize
the types of 3 latest faults (FL.14~FL.16), and the
voltage, current and frequency (FL.17~FL.19) of
the most recent fault.
See chapter 6 for the detailed introductions to the
alarm.
5.15 Operating Time (Fn)
Fn.00 Preset operating time Range: 0
~
65.535kh
【
0
】
Fn.01 Total operating time
Range: 0
~
65.535kh
【
0
】
Fn.02 Reserved
Fn.03 Reserved
If the accumulated operating time has amount to
Fn.00, the drive will give out an indicating signal.
Please refer to F7.10
~
F7.12.
Fn.01 is the total accumulated operating time
from delivery till now.
5.16 Protection of Parameters
(FP)
FP.00 User password
Range: 0000
~
9999
【
0000
】
User’s password can prevent unauthorized
persons from checking and modifying the
parameters.
Set FP.00 to 0000 if the user’s password is not
necessary.
If you want to set the user’s password, input a
4-digit number, press FUNC/DATA to confirm. If
not pressing any key within 5 minutes, the
password will become effective.
Changing the password: