Chapter 5 Parameters 53
EV1000 Series General Purpose Variable Speed Drive User Manual
Freq. (Hz)
Lower limit of freq. F
L
Upper limit of
freq. F
H
Step freq.=AW*F6.05
Waiting time
F6.03
Rising
time=F6.06*F6.07
Traverse
operating
cycle
Central Freq. Fset
Traverse amplitude Aw=Fset*F6.04
- Aw
+ Aw
Run
command
stop
command
t
Decelerate
according
to Dec time
a1
a1
Preset freq.
Accelerate
according
to Acc time
Fig. 5-36 Traverse Operation
The central frequency is the frequency of simple operation, MS running or PLC.
The traverse is invalid for jog or close-loop running.
When both PLC and traverse are enabled, the traverse is invalid when transferring to another PLC stage.
The output frequency begins to traverse after arriving at the PLC preset frequency within Acc/Dec time.
When receiving Stop command, the drive will stop according to PLC Dec time.
F6.00 Traverse function
selection
Range: 0
~
1
【0】
0: disabled
1: enabled
F6.01 Traverse mode
Range: 0000
~
1111
【0000】
This parameter is to set the operating mode of
traverse. Refer to the figure below.
Thou
Ten One
Start mode
0: auto
1: terminal config. (manually)
Restart mode
0: start to the state before power-off
1: restart, no other requirement
Amplitude
0: varied
(
based on central freq.)
1: fixed (based on max. freq.)
Save traverse state upon power failure
0: save
1: not save
Hun
Fig. 5-37 Traverse Mode Setting
One’s place of F6.01: transfer mode
0: auto
The drive will stay at traverse preset frequency
(F6.02) for a period of time (F6.03), and then
begin traverse automatically.
1: terminal configuration (manually)
When multi-function terminal is enabled and the