2: Meter Overview
2.3.3: Programmable Display
The Nexus® 1262/1272 meter features a built-in graphical back-lit FSTN LCD display
with extended temperature Voltage compensation. This allows you to view energy
data and to gather circuit diagnostic data such as Voltage, current, harmonics and
phasor information. The display is fully programmable. See Chapter 3 for details on
the programmable display.
2.3.4: Additional Switches
The Nexus® 1262/1272 meter has additional switches & signals that help in using the
unit (see Section 3.2 for more information):
• The Infrared Test Pulse can be set to pulse for +Watt-hour, -Watt-hour, +VAR-hour,
-VAR-hour and VA-hour. The pulse uses time modulation, which allows the pulse to
be accurate during short duration pulse tests. The pulse integration uses industry-
accepted reference standards.
• The Mode Switch (magnetic reed switch) uses a magnet to switch operating modes.
• The Test button is used to access Test Mode.
• The Reset button is used to reset Demand.
2.3.5: Nexus® External I/O Modules
A variety of optional analog or digital I/O modules mount externally to the Nexus®
1262/1272 Socket meter. The Nexus® 1262/1272 unit does not supply power to I/O
modules. Use a power supply, such as EIG’s PSIO, to power optional I/O modules. See
Chapter 10 for details on installation and use of the Nexus® External I/O modules.