10: Electrical Installation
Electro
Industries/GaugeTech
™
Powered by Innovation™
Figure 10.14: Form 45S Wye, 2 PTs, 3 CTs
• The protective ground connections for the transformers are omitted in the diagrams and are not required
for the meter to work properly. However, we strongly recommend those connections to reduce shock
hazard.
• Shorting switches (blocks) for the current transformers’ secondary side are also not shown. To prevent
electrical shock we recommended you use such shorting switches (blocks). Make sure the CTs’ second-
ary are shorted before disconnecting them from the meter’s current input terminals.
3
N
1
2
LOAD
LINE
FORM: 45S (TRANSFORMER RATED)
SERVICE: WYE, 4WIRE
2 PTs, 3 CTs