![Electro Industries/GaugeTech Nexus 1262 User Manual Download Page 105](http://html.mh-extra.com/html/electro-industries-gaugetech/nexus-1262/nexus-1262_user-manual_2379732105.webp)
Doc# E151701 5-7
5: Serial Communication Wiring
Electro
Industries/GaugeTech
™
Powered by Innovation™
Figure 5.7: Meter Connected to a PC Using Unicom 2500
The Unicom 2500 can be configured for either 4-wire or 2-wire RS485 connections.
Since the Nexus® meter uses a 2-wire connection, you need to add jumper wires to
convert the Unicom 2500 to the 2-wire configuration.
As shown in Figure 5.7, you connect the "RX-" and "TX-" terminals with a jumper wire
to make the "-" terminal, and connect the "RX+" and "TX+" terminals with a jumper
wire to make the "+" terminal. See the figure on the right for the Unicom 2500’s set-
tings. The Unicom’s Baud rate must match the Baud rate of the meter’s RS485 port:
you set the Baud rate by turning the screw to point at the rate you want.
5.3.3: RJ45 Connection—Meter with INP200 (10/100BaseT) Option
The INP200 Option conforms to the IEEE 802.3, 10/100BaseT specification using
unshielded twisted pair (UTP) wiring. This allows you to use inexpensive RJ45
(+)
(-)
SH
(+)
(-)
SH
Jumpers:
Short TX(-) to RX(-) becomes (-) signal
Short TX(+) to RX(+) becomes (+) signal
TX(-) RX(-) TX(+) RX(+) SH
RS232 Port
UNICOM 2500
PC
Meter’s RS485 Port