Figure 11.18: 36Z 2.5 Element Wye, 2 PTs, 3 CTs
• The protective ground connections for the transformers are omitted in the diagrams and are not required
for the meter to work properly. However, we strongly recommend those connections to reduce shock
hazard.
• Shorting switches (blocks) for the current transformers’ secondary side are also not shown. To prevent
electrical shock we recommended you use such shorting switches (blocks). Make sure the CTs’ second-
ary are shorted before disconnecting them from the meter’s current input terminals.
Vn
Vc
Lo
Lo
Lo
Vb
Va
Ia - Hi
Ib - Hi
Ic - Hi
Network Phone Line
L N PE
Power In
8 7 6 5 4 3 2 1 C
(-) (+)
IRIG-B
S (-) (+)
COM1
S (-) (+)
COM4
HIGH SPEED
|
|
|
Y K Z
CH1
Y K Z
CH2
Y K Z
CH3
Y K Z
CH4
|
|
|
S (1) (+)
Gateway
|
+
+
+
+
+
+
+
+
+
+
V1
N
V3
I2
I1
I3
LOAD
LINE
N
1
2
3
2
3
N
1
SERVICE: 2.5 EL WYE
2 PTs, 3 CTs
Caution: Power Supply Input
on new units is configured
differently.
Please check wiring carefully.