8: Transformer Loss Compensation
Electro
Industries/GaugeTech
™
Powered by Innovation™
Enter 3-Phase or 1-Phase values. If 3-Phase values are entered, calculate 1-Phase
values by dividing 3-Phase values by three. Convert 1-Phase Loss Watts to 1-Phase
kW by dividing 1-Phase Loss Watts by 1000.
Enter 3-Phase or 1-Phase values. If 3-Phase values are entered, calculate 1-Phase
values by dividing 3-Phase values by three. Convert 1-Phase Self-Cooled MVA to
1-Phase kVA by multiplying by 1000.
Test Voltage is generally Phase-to-Phase for three-phase transformers. Calculate
Phase-to-Neutral Voltage by dividing Phase-to-Phase Voltage by the square root of 3.
Calculate Full Load Current by dividing the (1-Phase kW Self-Cooled Rating) by the
(Phase-to-Neutral Voltage) and multiplying by 1000.
Table 3:
Value
Watts Loss
3-Phase
1-Phase
1-Phase kW
No-Load Loss
Load Loss
Table 4:
Value
3-Phase MVA
1-Phase MVA
1-Phase kVA
Self-Cooled Rating
Table 5:
% Exciting Current
% Impedance
Table 6:
Value
Phase-to-Phase
Phase-to-Neutral
Test Voltage (Volts)
Full Load Current (Amps)