![Electro Industries/GaugeTech Nexus 1262 User Manual Download Page 35](http://html.mh-extra.com/html/electro-industries-gaugetech/nexus-1262/nexus-1262_user-manual_2379732035.webp)
Doc# E151701 1-17
-
Electro
Industries/GaugeTech
™
Powered by Innovation™
1: Three-Phase Power Measurement
picture of the voltage or current waveform for viewing and harmonic analysis. Typi-
cally a waveform capture will be one or two cycles in duration and can be viewed as
the actual waveform, as a spectral view of the harmonic content, or a tabular view
showing the magnitude and phase shift of each harmonic value. Data collected with
waveform capture is typically not saved to memory. Waveform capture is a real-time
data collection event.
Waveform capture should not be confused with waveform recording that is used to
record multiple cycles of all voltage and current waveforms in response to a transient
condition.
1.5: Power Quality
Power quality can mean several different things. The terms "power quality" and
"power quality problem" have been applied to all types of conditions. A simple defini-
tion of "power quality problem" is any voltage, current or frequency deviation that
results in mis-operation or failure of customer equipment or systems. The causes of
power quality problems vary widely and may originate in the customer equipment, in
an adjacent customer facility or with the utility.