Doc# E151701 13-3
13: EN50160/IEC61000-4-15 Flicker
Electro
Industries/GaugeTech
™
Powered by Innovation™
The .3-second memory time constant in the flicker meter ensures that P(0.1) cannot
change abruptly and no smoothing is needed for this percentile.
• Long Term Flicker Evaluation: The 10-minute period on which the short-term flicker
severity is based is suitable for short duty cycle disturbances. For flicker sources
with long and variable duty cycles (e.g. arc furnaces) it is necessary to provide cri-
teria for long-term assessment. For this purpose, the long-term Plt is derived from
the short-term values over an appropriate period. By definition, this is 12 short-
term values of 10 minutes each over a period of 2 hours. The following formula is
used:
,where Psti (i = 1, 2, 3...) are consecutive readings of the short-term severity Pst.
13.2.1: Summary
Flicker
= Changes in the illumination of light sources due to cyclical Voltage
variations.
Pinst
= Instantaneous flicker values in Perceptibility Units (PU).
Pst
= Value based on 10-minute analysis.
Plt
= Value based on 12 Pst values.
Measurement Procedure:
1. Original Signal with amplitude variations.
2. Square demodulator.
3. Weighted filter.
4. Low pass filter 1st order.
5. Statistical computing.
3
1
3
N
P
P
N
i
sti
lt