![Electro Industries/GaugeTech Nexus 1262 User Manual Download Page 111](http://html.mh-extra.com/html/electro-industries-gaugetech/nexus-1262/nexus-1262_user-manual_2379732111.webp)
Doc# E151701 5-13
5: Serial Communication Wiring
Electro
Industries/GaugeTech
™
Powered by Innovation™
5.3.8: Steps to Determine Power Needed
Since the Nexus® 1262/1272 meter’s power supply does not supply power to the I/O
modules, you need to use a power source, such as EIG’s PSIO, which is designed for
use with the I/O modules. Follow these steps to determine how many PSIO units you
need.
1. All I/O modules are shipped pre-programmed with a baud rate of 57600 and
individual addresses. Refer to the following table to determine the VA Ratings for
the I/O modules.
2. Add together the VA Ratings for the I/O modules in use to determine total power
needed.
3. Each PSIO supplies 12 VA @ 12 V DC. For details on the PSIO, see sections 10.2.1
and 10.3.
I/O Module Factory Settings and VA Ratings
Model#
Module
Address
VA Rating
1mAON4
0-1 mA, 4 Analog
Outputs
128
2.7 VA
1mAON8
0-1 mA, 8 Analog
Outputs
128
3.2 VA
20mAON4
4-20 mA, 4 Analog
Outputs
132
5.0 VA
20mAON8
4-20 mA, 8 Analog
Outputs
132
8.5 VA
8AI1
0-1 mA, 8 Analog
Inputs
136
2.3 VA
8AI2
0-20 mA, 8 Analog
Inputs
140
2.3 VA
8AI3
0-5 V DC, 8 Analog
Inputs
144
2.3 VA
8AI4
0-10 V DC, 8 Analog
Inputs
148
2.3 VA
4RO1
4 Latching Relay
Outputs
156
2.7 VA
4PO1
4 KYZ Pulse Outputs
160
2.7 VA
8DI1
8 Status Inputs
(Wet/Dry)
164
1.0 VA