13: EN50160/IEC61000-4-15 Flicker
Electro
Industries/GaugeTech
™
Powered by Innovation™
13.8: Performance Notes
Pst and Plt average time are synchronized to the clock (e.g. for a 10 minute average,
the times will occur at 0, 10, 20, etc.). The actual time of the first average can be less
than the selected period to allow for initial clock synchronization.
If the wrong frequency is chosen (e.g. 50 Hz selection for a system operating at 60
Hz), Flicker will still operate but the computed values will not be valid. Therefore, you
should select the frequency setting with care.
User settings are stored. If Flicker is on and power is removed from the meter, Flicker
will still be on when power returns. This can cause gaps in the logged data.
The Max and Min values are stored, and are not lost if the unit is powered down.
Flicker is defined using the requirements of IEC 61000-4-15 and former IEC 868 and
is designed for survey purposes only. Refer to those specifications for more details, if
needed. Meters with the Flicker option also are designed to the requirements for the
IEC 61000-4-30 standards for Flicker for survey purposes only. Refer to chapters 16
and 17 in the
CommunicatorPQA®, MeterManagerPQA
®
, and EnergyPQA.com
®
Soft-
ware User Manual
for additional information.
Operation is at 230 V for 50 Hz and 120 V for 60 Hz as per specification. If the input
Voltage is different, the system will normalize it to 230 V or 120 V for computational
purposes.