Doc# E151701 10-1
10: Electrical Installation
Electro
Industries/GaugeTech
™
Powered by Innovation™
10: Electrical Installation
The Nexus® 1262/1272 meter supported forms and their wiring configurations are
shown in this chapter. The forms are based on the rated Voltage and hookup required
for your application. (Custom forms and configurations are also available from EIG.)
Socket meter wiring diagrams are shown in 10.3: Socket Meter Wiring Diagrams,
page 10-6 and SWB Switchboard wiring diagrams are shown in 10.5: SWB3 Switch-
board Meter Wiring Diagrams, page 10-25.
10.1: Considerations When Installing Meters
Installation of the Nexus® 1262/1272 meter must be performed only by
qualified personnel who follow standard safety precautions during all
procedures. Those personnel should have appropriate training and
experience with high voltage devices. Appropriate safety gloves, safety
glasses and protective clothing are recommended.
During normal operation of the Nexus® meter, dangerous voltages flow through
many parts of the unit, including: Terminals and any connected CTs (Current Trans-
formers) and PTs (Potential Transformers), all I/O Modules and their circuits.
All
Primary and Secondary circuits can, at times, produce lethal voltages and
currents. Avoid contact with any current-carrying surfaces
.
Do not use the meter or any I/O device for primary protection or in an
energy-limiting capacity. The meter can only be used as secondary protec-
tion.
Do not use the meter for applications where failure of the meter may cause harm or
death.
Do not use the meter for any application where there may be a risk of fire.
All meter terminals should be inaccessible after installation.
Do not apply more than the maximum voltage the meter or any attached device can
withstand. Refer to meter and/or device labels and to the Specifications for all devices
before applying voltages. Do not HIPOT/Dielectric test any Outputs, Inputs or Com-
munications terminals.