Doc# E151701 8-9
8: Transformer Loss Compensation
Electro
Industries/GaugeTech
™
Powered by Innovation™
Load Loss at Transformer
No-Load Loss Watts (kW)
= 1-Phase kW No-Load Loss = ______________
No-Load Loss VA (kVA)
= (%Exciting Current) * (1-Phase kVA Self-Cooled Rating)
/ 100 = (______________) * (________________) / 100
= _______________ kVA
No-Load Loss VAR (kVAR)
= SQRT((No-Load Loss kVA)2 - (No-Load Loss kW)2) =
SQRT((_________________)2 - (________________)2)
= SQRT((__________________) - (_________________))
= SQRT (_________________) = ____________________
Full-Load Loss Watts (kW)
= 1-Phase Kw Load Loss = ______________
Full-Load Loss VA (kVA)
= (%Impedance) * (1-Phase kVA Self-Cooled Rating) /
100 = (______________) * (________________) / 100
= _______________ kVA
Full-Load Loss VAR (kVAR)
= SQRT((Full-Load Loss kVA)2 - (Full-Load Loss kW)2)
= SQRT((_________________)2 - (________________)2)
= SQRT((__________________) - (_________________))
= SQRT (_________________) = _________________