5.8.5.2 Master-slave mode for the synchronisation of several controllers
Function description
Master configuration:
The internal defrost timer must be active on one of the participating case
controllers (menu 3-2, parameter Defrost Timer = INT). This controller is then the master.
Slave configuration:
The other case controllers must be configured for external defrost start (menu 3-2,
parameter Defrost Timer = EXT). These are then automatically slave case controllers.
On reaching the defrost end temperature for the respective zone the defrost relay is switched off. Cooling is
only resumed when all the control zones of all the participating case controllers have completed the defrost or
the safe defrost time has elapsed.
Defrosting example
Case controller UA M configured as master. Case controller UA S configured as slave. The start of the
synchronised master/slave defrost is initiated via the internal timer.
Note the following for this example:
The internal defrost signal is applied for the entire safe defrost time. Termination of defrosting is generally
governed however by de-energizing of the last defrost relay.
Further details of special features and restrictions are provided in chapter
synchronisation of the zones of a single contr.
.
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Page 207: ...Firmware V3 13 21 04 2021 207 466 ...
Page 277: ...Firmware V3 13 21 04 2021 277 466 ...