Menu 1-7 Cooling Zone 2
COOLING 2 XXXXX
Cooling XXX
Displays current OFF/ON status of cooling
op.deg. Z 2 XX %
Displays current valve opening degree Zone 2
OD med. 24h XX %
Displays mean valve opening degree Zone 2 for past day
Temp. R4.2 XXX °C
Displays current room air temperature Input Z71/Z72
Setpoint R4.2 XXX °C
Displays room air temperature setpoint for comparison
Hystersis R4.2 XXX K
Displays room air temperature hysteresis setpoint; shown only when on-off control
is set (Menu 2-1-2)
SH Z 2 XXX °C
Displays current superheat temperature Zone 2
sup air ctrl XXX
Displays current OFF/ON status of supply or room air control
MOP op. XXX
Displays OFF/ON setpoint of MOP mode
Status hand XXX
Status manual shutdown (ON/OFF)
Menu 1-8 Defrost Zone 2
DEFROST 2 XXXXX
Counting Rate X
Displays setpoint for time during which evaporator defrost termination temperature
may be within band around 0°C before defrost counter counts down
Defrost Counter X
Displays count for number of defrost cycles to be skipped
Defrost XXX
Displays current OFF/ON status of Defrost Relay 2
Temp. R1.2 XXX °C
Displays current evaporator defrost termination temperature Input Z81/Z82
Def. End. Tmp. XXX °C
Displays defrost termination temperature setpoint for comparison
Wait Time XX m
Displays waiting time setpoint
Drip Time XX m
Displays drip time setpoint
Last Defrst XX hh:mm
Displays time (day, time of day) of last defrost cycle started
Menu 1-9 Fan Zone2
FANS 2 XXXXX
Fans XXX
Displays current fan status
Temp. R1.2 XXX °C
Displays current evaporator defrost termination temperature Input Z81/Z82
Fan Delay XXX °C
Displays fan start temperature setpoint
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Page 207: ...Firmware V3 13 21 04 2021 207 466 ...
Page 277: ...Firmware V3 13 21 04 2021 277 466 ...