Firmware V3.13
21.04.2021
381/466
•
Menu 6-2-8 EEV Controller Zone 2
EEV ZONE 2 POS: XXXXX
Entry
Default
Pc Z 2: XX.XX
Temperature control Zone 2, P-part
0..99.99
7.00
Ic Z 2: XX.XX
Temperature control Zone 2, I-part
If parameter I
c
is reduced, internal learned value
(sum of I-part) is deleted and re-learned in due
course.
0..99.99
0.30
Dc Z 2: XX.XX
Temperature control Zone 2, D-part
0..99.99
5.00
offs OD cab. XX %
Percentage valve opening degree offset for
temperature control
If offset is changed, internal learned value (sum of
I-part) is deleted and re-learned in due course.
0..100
30 %
Psh Z 2: XX.XX
Superheat control Zone 2, P-part
0..99.99
5.00
Ish Z 2: XX.XX
Superheat control Zone 2, I-part
If parameter I
sh
is reduced, internal learned value
(sum of I-part) is deleted and re-learned in due
course.
0..99.99
0.10
Dsh Z 2: XX.XX
Superheat control Zone 2, D-part
0..99.99
5.00
offs OD SH XX %
Percentage valve opening degree offset for
superheat control
If offset is changed, internal learned value (sum of
I-part) is deleted and re-learned in due course.
0..100
10 %
emerg.c-o OD XX %
Maximum valve opening degree
0..50
20 %
delay min SH XX s
Delay on drop of superheat below set minimum
9..600
9 sec
edit op.deg. XXX
Manual entry of valve opening degree
↑, ↓,
(ON/OFF)
OFF
op.deg. Z 2 XXX %
Current valve opening degree Zone 2; can be
edited when manual entry is activated
0..100
Default ctrlr.
•
•
This menu is only visible if
the “Master” mode is activated in the system centre, i.e.
the “Superuser mode” is activated in the store computer.
chapter.
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Page 207: ...Firmware V3 13 21 04 2021 207 466 ...
Page 277: ...Firmware V3 13 21 04 2021 277 466 ...