Firmware V3.13
21.04.2021
325/466
•
•
•
•
•
•
•
•
•
Menu 3-2-a Def.Tim.Z2
DEFR.TIMER POS: XXXXX
Entry
Default
Defrost Timer XXX
Setting for how temperature zone 2 should defrost:
MitZ1 Together with zone 1
INT Internally
EXT Externally – the defrost of both
temperature zones is started
simultaneously via the external signal
↑, ↓,
(ViaZ1(ViaZ1,
EXT,
INT)
ViatZ1
Safe Defr Time XXX m
Safe defrost time, i.e. max. allowed duration of
defrosting
(internal defrost only)
0..120
60 min
Manual Defrost XXX
Status (ON/OFF) of auxiliary manual defrost *)
↑, ↓,
(ON/OFF)
OFF
Defr. 1 xxxxx hh:mm
Defrost start time for internal defrost; weekday, time
of day;
shown only when paramter
defrost timer
= INT
↑, ↓,
(Mo-Su) or
numbers
(hh:mm)
Mo-Su
01:00
...
Defr. 14 xxxxx hh:mm
Menu 3-3 Setpoint Toggle
TOGGLE POS: XXXXX
Entry
Default
Status XXX
Setpoint toggle for alternative set of setpoints
(setpoint set
toggle)
Toggle Setp. XXX
Setpoint toggle via:
EXT digital input D21/22
INT= internal timer
CAN= CAN bus
„—"= deactivated
↑, ↓,
(EXT, INT, CAN, --)
EXT
Toggle interv. X m
The interval for the cyclical toggling between
standard and alternative setpoint data records; only
appears when the internal setpoint toggling is
activated (menu 3-3).
--, 10..60
– min
Alt ON: xxxxx hh:mm
Start time for toggle to alternative set of setpoints,
weekday from-to DD-DD, time hh:mm; shown only
when internal setpoint toggle is activated (Menu 3-3)
↑, ↓,
(Mo-Su) or
numbers
(hh:mm)
Mo-Su
21:00
AltOFF: xxxxx hh:mm
End time for toggle to alternative set of setpoints,
weekday from-to DD-DD, time hh:mm; shown only
when internal setpoint toggle is activated (Menu 3-3)
↑, ↓,
(Mo-Su) or
numbers
(hh:mm)
Mo-Su
05:00
Alt ON: xxxxx hh:mm
Start time for toggle to alternative set of setpoints,
weekday from-to DD-DD, time hh:mm; shown only
when internal setpoint toggle is activated (Menu 3-3)
↑, ↓,
(Mo-Su) or
numbers
(hh:mm)
Su
05:00
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Page 207: ...Firmware V3 13 21 04 2021 207 466 ...
Page 277: ...Firmware V3 13 21 04 2021 277 466 ...