Firmware V3.13
21.04.2021
112/466
If, for example, the case controller is required to switch off the cooling on receiving an emergency power
message,
then the parameter Cool.funct.OFF must be set to Y (Yes). If this parameter is set to N (No), then the
case controller continues cooling even during emergency power operation.
All other parameters in principle function the same. They determine whether the defrosting or the fan is
switched off during emergency power operation. If the controller is conducting a defrost at the start of
emergency power operation then the defrost is immediately interrupted. If the defrost command comes during
emergency power operation then the command is ignored.
Defrosts that are ignored or interrupted due to emergency power operation are not automatically
repeated by the controller. If a defrost interruption occurs due to emergency power operation then the
refrigeration capacity of the corresponding refrigeration points must be checked.