Firmware V3.13
21.04.2021
228/466
9.2 Contr. Type UA 131 E / UA 131 E LS - Menu tree
DIP switch S3
UA 131 E
1: OFF
2: ON
3: OFF
4: ON/OFF =
ON/OFF
5: OFF
6: ON/OFF =
Funktionsweise der Analogausgänge 0..10 V
7..8: OFF
9: ON
UA 131 E LS
1: ON
2: ON
3: ON
4: ON/OFF =
EIN/AUS
5: ON =
Betrieb mit bis zu vier Rückluftfühlern - nur UA 131 E LS
Funktionsweise der Analogausgänge 0..10 V
7..8: OFF
9: ON
Main Menu
Submenu 1
Submenu 2
Menu No.
Menu Name
Actual Values
1
ACT VALUES
Temperature Sensors
1-1
TEMPERATUR
Cooling Zone 1
1-2
COOLING 1
Defrost Zone 1
1-3
DEFROST 1
Fan
1-4
FANS
Alarm
1-5
ALARM
Frame Heater
1-6
MODE
Cooling Zone 2
1-7
COOLING 2
Defrost Zone 2
1-8
DEFROST 2
Setpoints
2
SETPOINTS
Cooling
2-1
COOLING
Zone 1
2-1-1
COOLING 1
Zone 2
2-1-2
COOLING 2
Zone 1T Toggle
2-1-3
COOLING 1A
Zone 2T Toggle
2-1-4
COOLING 2A
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Page 207: ...Firmware V3 13 21 04 2021 207 466 ...
Page 277: ...Firmware V3 13 21 04 2021 277 466 ...