Firmware V3.13
21.04.2021
197/466
•
•
9.1.3 Menu 2 Setpoints UA 121 E
SETPOINTS POS: XXXXX
1 Cooling
Move to menu 2-1;
Special case:
When one-zone (tandem) operation is set (Menu
6-1) and setpoint toggle is deactivated (Menu 3-3), Continue to 2-1-1
2 Defrost
Move to menu 2-2;
Special case:
When one-zone (tandem) operation is set (Menu
6-1) and setpoint toggle is deactivated (Menu 3-3), Continue to 2-2-1
3
Not used with this controller type
4 Alarm
Move to menu 2-4;
Special case:
When one-zone (tandem) operation is set (Menu
6-1) and setpoint toggle is deactivated (Menu 3-3), Continue to 2-4-1
5 Rahmenheizung
Move to menu 2-5
Menu 2-1 Cooling
COOLING POS: XXXXX
1 Zone 1
Move to menu 2-1-1
2 Zone 2
Move to menu 2-1-2
3 Zone 1T Toggle.
Move to menu 2-1-3; not shown when setpoint toggle is deactivated (Menu 3-3)
3 Zone 2T Toggle
Move to menu 2-1-4; shown only when two-zone operation is set and when setpoint
toggle is not deactivated (Menu 3-3)
Menu 2-1-1 Zone 1
COOLING 1 POS: XXXXX
Entry
Default
Setpoint R2.1 XXX °C
Supply air temperature setpoint
--, -10..20
-2 °C
Hystersis R2.1 X K
Supply air temperature hysteresis setpoint; shown only
when on-off control is set (Menu 2-1-1)
1..8
4 K
Setpoint R4.1 XXX °C
Return air temperature setpoint
--, -10..20
4 °C
Hystersis R4.1 X K
Return air temperature hysteresis setpoint; shown only
when on-off control is set (Menu 2-1-1)
1..8
2 K
Superheat XXX K
Superheat setpoint Zone 1
0..20
6 K
Min. SH XX K
Minimum superheat setpoint, below which cooling
relay
switches off in Zone 1. I-sum (not I-part) is set to zero
when the Reset I-Sum parameter is set to ON.
0..10
2 K
Two pos.ctrl XXX
Switch between on-off control (ON) and continuous
control (OFF)
↑, ↓ (ON/OFF)
OFF
MOP-point XXX °C
Starting setpoint for MOP mode
--, -50..50
– °C
Cool. on AOUT XXX%
Kühlung eingeschaltet: fester Wert 0..10 V für
Analogausgang AO1; nur sichtbar, wenn von DIP-
Schalter S3 der Kodierschalter 6 auf ON steht, siehe
Kapitel
Funktionsweise der Analogausgänge 0..10 V.
0..100
80 %
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Page 207: ...Firmware V3 13 21 04 2021 207 466 ...
Page 277: ...Firmware V3 13 21 04 2021 277 466 ...