Firmware V3.13
21.04.2021
365/466
•
•
•
Menu 2-5-2 Frame Setpoints
SETPOINTS POS: XXXXX
Entry
Default
Mod: xxxxxxxxxxxx
Displays set pane mode (Menu 2-5-1)
fixed run time
Run Time XXX %
Fixed on time; shown only when mod is set to
Fixed OT (Menu 2-5-1)
--, 0..100
100 %
emerg.run time XXX %
On time in loss of humidity or room air
temperature (via CAN bus); shown only when
mode set to Enthalpy Control (Menu 2-5-1)
--, 0..100
100 %
enthalp. offs. XXX %
Offset for on time when enthalpy control is
activated (via CAN bus); shown only when mode
set to Enthalpy Control (Menu 2-5-1)
-50..50
0 %
Invert Output xxx
Inversion of the function of the frame heater
output
(terminals 91/92)
↑, ↓
(ON/OFF)
ON
Menu 2-5-3 Toggle Mode
Selection is made according to entry. Checkmark shows current setting.
MODE ALT. POS: XXXXX
Entry
Default
Fixed run time
Enthalpy-ctrl rtm
Menu 2-5-4 Setpoint Toggle
TOG. SETP. POS: XXXXX
Entry
Default
Mod: xxxxxxxxxxxx
Displays set pane mode (Menu 2-5-3)
fixed run time
Run Time XXX %
Fixed on time; shown only when mod is set to
Fixed OT (Menu 2-5-3)
--, 0..100
100 %
emerg.run time XXX %
On time in loss of humidity or room air
temperature (via CAN bus); shown only when
mode set to Enthalpy Control (Menu 2-5-3)
--, 0..100
100 %
enthalp. offs. XXX %
Offset for on time when enthalpy control is
activated (via CAN bus); shown only when mode
set to Enthalpy Control (Menu 2-5-3)
-50..50
0 %
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Page 207: ...Firmware V3 13 21 04 2021 207 466 ...
Page 277: ...Firmware V3 13 21 04 2021 277 466 ...