Menu 1-2 Cooling Zone 1
COOLING 1 XXXXX
COOLING XXX
Displays current OFF/ON status of cooling
op.deg. Z 1 XX %
Displays current valve opening degree Zone 1
OD med. 24h XX %
Displays mean valve opening degree Zone 1 for past day
Temp. R2.1 XXX °C
Displays current supply air temperature Input Z11/Z12
Setpoint R2.1 XXX °C
Display supply air temperature setpoint for comparison
Hystersis R2.1 XXX K
Displays supply air temperature hysteresis setpoint; shown only when on-off
control is set (Menu 2-1-1)
Temp. R4.1 XXX °C
Displays current return air temperature Input Z21/Z22
Setpoint R4.1 XXX °C
Displays return air temperature setpoint for comparison
Hystersis R4.1 XXX K
Cisplays return air temperature hysteresis setpoint; shown only when on-off control
is set (Menu 2-1-1)
SH Z 1 XXX °C
Displays current superheat temperature Zone 1
sup air ctrl XXX
Displays current OFF/ON status of supply or return air control
MOP op. XXX
Displays OFF/ON setpoint of MOP mode
Status light XXX
Status lighting control (ON/OFF)
Status hand XXX
Status manual shutdown (ON/OFF)