Firmware V3.13
21.04.2021
442/466
ANALOG INPUTS POS: XXXXX
Entry
Default
RfrSy. tcLT xxx
Pack controller CAN bus address for receipt of tc
via CAN bus
Can also be used as backup option in the event of
the failure of the local pressure transmitter
Deactivated with '--'
Can only be used when parameter ”Fct. AIN2” set
to ”tc LT”.
--, 1..9
--
tcZ2-max xxx°C
tc maximum value for the dynamically determined
tc setpoint
-10..10
-2 °C
tcZ2-min xxx°C
tc minimum value for the dynamically determined tc
setpoint
-20..10
-10 °C
tcZ2-ramp/m xxxK
Maximum increase / change of the dynamically
evaluated tc setpoint
Dynamic evaluation of the tc setpoint switched off
with '--'; in this case the setpoint R4.x is used.
Can only be used when parameter ”Fct. AIN2” set
to ”tc LT”.
--1..100
--
tcZ2-toZ1df xxxK
Difference between to and tc for the dynamic
determination of the tc setpoint
0..20
5 K
*Supported refrigerants: R404A, R744 (CO2), R134a, R410A, R717 (NH3), R22, R290, R407C, R507, R1270,
R402A, R502, R407F, R422A, R422D, R408A, R407D, R407A, R427A, R438A, R152a, R170, R600, R600a,
R449A, R450A, R448A, R455A, R447B, R1234ze, R1233zd, R1234yf, R513A
Praxis tip using the example of the ”connection of a pressure transmitter - 1 .. 7 bar”:
Here the indication on the pressure transmitter is clear (-> -1 bar) relative to the ambient pressure The
adjustment of the pressure transmitter in the controller is carried out using absolute pressure values
(the absolute pressure cannot be negative). In order to parameterise the above pressure transmitter
with the relative pressure indication - 1 bar (at 4 mA, i.e. 0 V) at 7 bar ( at 20mA, i.e. 10 V) the ambient
pressure (1 bar) must be added.
The entry is carried out as follows: 0..8 bar.
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Page 207: ...Firmware V3 13 21 04 2021 207 466 ...
Page 277: ...Firmware V3 13 21 04 2021 277 466 ...