5.11.5 Registration of external alarms (e.g. CO2 alarm)
A voltage applied at the 230 V AC input serves to register external alarms e.g. CO2 alarms. The message
text (CO
2
alarm, factory setting) can be freely entered in menu 6-2-4 (also with the BT 300).
DANGER
Warning – hazardous electrical voltage!
Danger of electric shock! BEFORE
connecting and
disconnecting it must be checked that the 230 V AC digital inputs are off load! The controller and
connected voltage carrying components remain supplied with power!
The external alarm can be activated via digital input 4 (terminals D41/D42, see chapter
). If the digital input is used for the monitoring of e.g. a CO
2
alarm, then for
safety reasons its function should be inverted to “ON” via the parameter Inv. D4 (menu 6-2-4).
Note
: If the controller is in
, there is
no
alarm!