Firmware V3.13
21.04.2021
275/466
•
Menu 1-3 Defrost Zone 1
DEFROST 1 XXXXX
Defrost Counter X
Displays count for number of defrost cycles to be skipped
Temp. R1.1 XXX °C
Displays current evaporator defrost termination temperature Input Z31/Z32
Temp. R1.2 XXX °C
Displays current evaporator defrost termination temperature Input Z81/Z82; shown
only when single-zone operation is set (Menu 6-1)
Def. End. Tmp. XXX °C
Displays defrost termination temperature setpoint for comparison
Wait Time XX m
Displays waiting time setpoint
Drip Time XX m
Displays drip time setpoint
Last Defrst XX hh:mm
Displays time (day, time of day) of last defrost cycle started
M/S Nof. Sl.
Number of parameterised and accessible MA slaves
M/S Lost Sl.
CAN address of the first MA slave which was not accessible during the last defrost
M/S Defr.Sl.
Number of slaves currently undergoing a defrost
M/S DSlMat
List of MA slaves currently undergoing a defrost
(can be scrolled through using ENTER)
DSq Nof. Sl.
Number of DS slaves (only in the case of DS master)
DSq Lost Sl.
CAN address of the first FA slave which was not accessible during the last defrost
DSq Defr.Sl.
Number of slaves currently undergoing defrost
DSq DSlMat
List of FA slaves currently undergoing a defrost
(can be scrolled through using ENTER)
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Page 207: ...Firmware V3 13 21 04 2021 207 466 ...
Page 277: ...Firmware V3 13 21 04 2021 277 466 ...