Firmware V3.13
21.04.2021
136/466
7.
Select menu
6 Configuration – 3 Cooling
.
6 Configuration - 3 Cooling
KÜHLUNGPOS: XXX
Korroff. to XXK
Correction offset which is applied to the t0 actual value received from the pack
controller via CAN bus. This enables pressure losses in the refrigerant line to be
compensated. If this value is set to "–", the case controller regulates using the
temperature sensors at the evaporator input and output (standalone operation).
Dauerl.Überw. XXm
Continuous use monitoring
DG-Betrieb AUS
This must be set for UA 131 E to guarantee that the D2D defrost runs correctly. The
defrost timer should be set to EXT when activating this operating mode.
Lüfterverzöger XX°C
Maximum value at the defrost sensor, at which the fan should be switched on after a
delay (e.g. after the defrost)
8.
Exit the
Configuration
menu by tapping the
ESC
button twice and select
3 Clock – 2 Defrost timer
Input of the relevant parameters in the following screen.
3 Clock - 2 Defrost Timer
ABTAUUHRPOS: XXX
AbtauuhrINT
Selection of defrost using external or internal defrost timer
Sicherheitsz.60m
Safe defrost time; the defrost is not longer than this time.
Defrost 1 DD-DD hh:mm
Entry of defrost times
Defrost 2 DD-DD hh:mm
...
Defrost 14 DD-DD hh:mm
man. AbtauungAUS
Manual defrost ON/OFF
9.
Exit from the
2 Defrost Timer
menu by tapping the
ESC
button.
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Page 207: ...Firmware V3 13 21 04 2021 207 466 ...
Page 277: ...Firmware V3 13 21 04 2021 277 466 ...