OPERATION
EATON
Powerware
®
BladeUPS
®
(12 kVA) User's Guide
S
164201649 Rev 3
www.powerware.com
75
Table 4. User Settings (continued)
Default Setting
Available Settings
Description
Modem Config
Modem Installation: [Not Installed] [X-Slot-1]
[X-Slot-2]
Not Installed
Set Modem Call Events
Event #0
Call modem: no
Set Modem Init String
ATZ0
Set Modem Call Command
None
Set Modem Communication Password
None
Battery Setup
Number of ERMs: [0 through 4] (see
“Configuring the UPS for EBMs” on page 87)
0
(means internal batteries only)
Battery Low Alarm Level:
[1.750 through 1.950 volts per cell] (see
“Setting the Battery Low Alarm Level” on
page 88)
1.880 V/cell
(provides approximately
2.5 min warning for the UPS)
Automatic Battery Tests: [Enabled] [Disabled]
(see “Running Automatic Battery Tests” on
page 87)
Enabled
(automatically runs the battery
test once a month)
Power Strategy
[High Efficiency] [Standard]
The Standard setting is limited to 60 minutes
when selected through the front panel. See
the following section, “Operating Modes.”
High Efficiency
Start Screen
Eaton Powerware logo
Mimic screen (see Figure 46 on page 71)
Eaton Powerware logo
User Password
[Enabled] [Disabled]
If Enabled is selected, the password is USER.
Disabled
Audible Alarms
[Normal Sound] [Disabled]
Normal Sound
Unsynchronized Transfer to Bypass
[Allowed] [Not Allowed]
Not Allowed
Transfer to Bypass When Overload
[After a delay] [Immediately]
After a delay
Automatic Start Delay
-1 through 32767 seconds
(-1 means disabled)
0s
Control Commands from X-Slot1
Control Commands from X-Slot2/Serv
[Allowed] [Not Allowed]
Selecting Not Allowed prevents load
commands such as Load Off through the
X-Slot, including remotely.
Allowed
X-Slot Signal Input Activation Delay
0 through 65 seconds
5s