COMMUNICATION
EATON
Powerware
®
BladeUPS
®
(12 kVA) User's Guide
S
164201649 Rev 3
www.powerware.com
94
Control Terminals
The cables should be connected to the control terminals with a mating
connector. Input and output terminals have a functional isolation from
terminal to terminal. They are connected to the UPS chassis through
individual 1 M
Ω
resistors.
+ Polarity
– Polarity
2
1
+ Polarity
– Polarity
2
1
2
1
2
1
Signal Input 1 (programmable)
Signal Input 2 (programmable)
REPO Normally Open
REPO Normally Closed
Normally Open
Normally Closed
1
2
Common
3
Relay Output
UPS
Connectors
(see Figure 47 on
page 89)
+ Polarity
– Polarity
2
1
Redundant Signal Wiring
(For Parallel Use Only)
+ Polarity
– Polarity
2
1
Standalone/Parallel
Figure 51. External Control Terminal Connections
NOTE
If using a semiconductor switch type, pay attention to the proper polarity. A relay or
other mechanical control is preferred.