SPECIFICATIONS
EATON
Powerware
®
BladeUPS
®
(12 kVA) User's Guide
S
164201649 Rev 3
www.powerware.com
117
Table 14. Environmental and Safety
BladeUPS 12
BladeUPS 12i
Surge Suppression
ANSI C62.41 Category B3
EN 61000-4-6
Safety Conformance
UL 1778 4
th
edition; CSA C22.2, No. 107.3
EN and IEC 62040-1-1
Agency Markings
cULus, ICES, VCCI
GS, CE
EMC (Class A)
FCC Part 15
EN 62040-2
Operating Temperature
0°C to 40°C (32°F to 104°F)
Optimal battery performance: 5°C to 25°C (41°F to 77°F)
Storage Temperature
0°C to 25°C (32°F to 77°F)
Transit Temperature
-25°C to 55°C (-13°F to 131°F)
Relative Humidity
Operating: 5–95% noncondensing
Non-operating: 5–95% relative humidity, 38.7°C (101.7°F)
Maximum wet bulb temperature with no cosmetic damage
Operating Altitude
Up to 1,000 meters (3,300 ft) above sea level;
up to 2,000 meters (6,600 ft) with 1% derating per +100 meters (330 ft)
Transit Altitude
Up to 15,000 meters (49,000 ft) above sea level
Heat Dissipation
1432 BTU/hr maximum at 100% rated load (High Efficiency mode)
4094 BTU/hr maximum at 100% rated load (Standard mode)
Audible Noise
Less than 58 dBA at 1 meter typical (Normal mode)
Less than 64 dBA at 1 meter typical (Battery mode)
Leakage Current
<3.5 mA
Communication
DB-9: 1200–19200 baud