EDR-5000
IM02602007E
Direct Commands of the IEC 61850
Parameter
Description
Setting range
Default
Menu path
ResetStatistic
Reset of all IEC61850 diagnostic counters
Inactive,
Active
Inactive
[Operation
/Reset]
Global Protection Parameters of the IEC 61850
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Device Para
/IEC61850]
Deadb integr time
Deadband integration time.
0 - 300
0
[Device Para
/IEC61850]
Global Parameters of the IEC 61850
Parameter
Description
Setting range
Default
Menu path
VirtualOutput1
Virtual Output. This signal can be assigned or visualized
via the SCD file to other devices within the IEC61850
substation.
1..n, Assignment
List
-.-
[Device Para
/IEC61850]
VirtualOutput2
Virtual Output. This signal can be assigned or visualized
via the SCD file to other devices within the IEC61850
substation.
1..n, Assignment
List
-.-
[Device Para
/IEC61850]
VirtualOutput3
Virtual Output. This signal can be assigned or visualized
via the SCD file to other devices within the IEC61850
substation.
1..n, Assignment
List
-.-
[Device Para
/IEC61850]
VirtualOutput4
Virtual Output. This signal can be assigned or visualized
via the SCD file to other devices within the IEC61850
substation.
1..n, Assignment
List
-.-
[Device Para
/IEC61850]
www.eaton.com
296