EDR-5000
IM02602007E
Options of the DNP
Name
Description
-.-
No assignment
Prot.FaultNo
Waveform No.
Prot.No of GridFaults
Number of grid faults: A grid fault, e.g. a short circuit, might cause several faults with trip and autoreclosing,
each fault being identified by an increased fault number. In this case, the grid fault number remains the same.
Bkr.TripCmd Cr
Counter: Total number of trips of the switchgear (breaker, load break switch…). Resettable with Total or All.
LVRT [1].NumOf Vdips in t-
LVRT
Number of Voltage dips during t-LVRT
LVRT [1].Cr Tot Numb of Vdips Counter Total number of voltage dips.
LVRT [1].Cr Tot Numb of Vdips
to Trip
Counter Total number of voltage dips that caused a Trip.
LVRT [2].NumOf Vdips in t-
LVRT
Number of Voltage dips during t-LVRT
LVRT [2].Cr Tot Numb of Vdips Counter Total number of voltage dips.
LVRT [2].Cr Tot Numb of Vdips
to Trip
Counter Total number of voltage dips that caused a Trip.
AR.AR Shot No.
Counter - Auto Reclosure Attempts
AR.Total number Cr
Total number of all executed Automatic Reclosures Attempts
AR.Cr successfl
Total number of successfully executed Automatic Reclosures
AR.Cr failed
Total number of unsuccessfully executed automatic reclosure attempts
AR.Cr Service Alarm1
Remaining numbers of ARs until Service Alarm 1
AR.Cr Service Alarm2
Remaining numbers of ARs until Service Alarm 2
AR.Max Shots / h Cr
Counter for the maximum allowed shots per hour.
ECr.Wh Fwd
Positive Active Power is consumed active energy
ECr.Wh Rev
Negative Active Power (Fed Energy)
ECr.VArh Lag
Positive Reactive Power is consumed Reactive Energy
ECr.VArh Lead
Negative Reactive Power (Fed Energy)
Sys.Operating hours Cr
Operating hours counter of the protective device
Selectable Switchgears of the DNP
Name
Description
-.-
No assignment
Bkr.State
Signal: Breaker Position (0 = Indeterminate, 1 = OPEN, 2 = CLOSE, 3 = Disturbed)
www.eaton.com
348