EDR-5000
IM02602007E
The following menu and tables show the detailed information about the settings.
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/stage.
The elements, that are associated with Zone Interlocking
depend on the protective device. Transformer relays:
ZI[1]: 50P[1], 50P[2], 51P[1], 50X[1], 51X[1], 50R[1],
51R[1] ZI[2]: 50P[3], 50P[4], 51P[3], 50X[2], 51X[2],
50R[2], 51R[2] All other Protective Devices: ZI: 50P[1],
50P[2], 51P[1], 50X[1], 50X[2], 51X[1], 50R[1], 50R[2],
51R[1]
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/ZI
/General Settings]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/ZI
/General Settings]
Blo TripCmd
Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/ZI
/General Settings]
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/ZI
/General Settings]
ZI OUT Fc
Zone Interlocking Out activate (allow) / inactivate
(disallow)
Inactive,
Active
Active
[Protection Para
/<1..4>
/ZI
/Zone Out]
Fault Type
Fault Type
Phase,
Ground,
Both
Both
[Protection Para
/<1..4>
/ZI
/Zone Out]
www.eaton.com
533