Module Automatic Reclosure Signals (Output States)
Signal
Description
Active
Signal: Active
ExBlo
Signal: External Blocking
Standby
Signal: Standby
t-Man Close Blo
Signal: AR blocked after breaker was switched on manually. This timer will be started if the
breaker was switched on manually. While this timer is running, AR cannot be started.
Ready
Signal: Ready to shoot
Running
Signal: Auto Reclosing Running
t-dead
Signal: Dead time between trip and reclosure attempt
Bkr CLOSE Cmd
Signal: Bkr. Switch ON (CLOSE) Command
t-Run2Ready
Signal: Examination Time: If the Breaker remains after a reclosure attempt (shot) for the duration
of this timer in the Closed position, the AR has been successful and the AR module returns into
the ready state.
Lock
Signal: Auto Reclosure is locked out
t-Reset Lockout
Signal: Delay Timer for resetting the AR lockout. The reset of the AR lockout state will be delayed
for this time after the reset signal (e.g digital input or Scada) has been detected .
Blo
Signal: Auto Reclosure is blocked
t-Blo Reset
Signal: Delay Timer for resetting the AR blocking. The release (de-blocking) of the AR will be
delayed for this time, if there is no blocking signal anymore.
successful
Signal: Auto Reclosing successful
failed
Signal: Auto Reclosing Failure
t-AR Supervision
Signal: AR Supervision
Pre Shot
Pre Shot Control
Shot 1
Shot Control
Shot 2
Shot Control
Shot 3
Shot Control
Shot 4
Shot Control
Shot 5
Shot Control
Shot 6
Shot Control
Service Alarm 1
Signal: AR - Service Alarm 1, too many switching operations
Service Alarm 2
Signal: AR - Service Alarm 2, too many switching operations
Max Shots / h exceeded
Signal: The maximum allowed number of shots per hour has been exceeded.
Res Statistics Cr
Signal: Reset all statistic AR counters: Total number of AR, successful and unsuccessful no of
AR.
Res Service Cr
Signal: Reset the Service Counters for pickup and blocking
Reset Lockout
Signal: The AR Lockout has been reset via the panel.
Res Max Shots / h
Signal: The Counter for the maximum allowed shots per hour has been reset.
ARRecCState
Signal: AutoReclosing states defined by IEC61850:1=Ready/2=In Progress/3=Successful