EDR-5000
IM02602007E
Parameter
Description
Setting range
Default
Menu path
Pickup P<
Under(load) Active Power Pickup Value (e.g.: caused by
idling motors). Definition for Sn is as follows: Sn = 1.7321
* VT rating * CT rating. The voltage is the line-to-line
voltage.
Only available if: Device Planning: PQS.Mode = Pickup
P<
0.003 - 10.000VAn
0.80VAn
[Protection Para
/<1..4>
/Power-Prot
/32[1]]
Pickup Pr>
Overload Reverse Active Power Pickup Value. Protection
against reverse feeding into the power supply network.
Definition for Sn is as follows: Sn = 1.7321 * VT rating *
CT rating. The voltage is the line-to-line voltage.
Only available if: Device Planning: PQS.Mode = Pickup
Pr>
0.003 - 10.000VAn
0.020VAn
[Protection Para
/<1..4>
/Power-Prot
/32[1]]
Pickup Pr<
Under Reverse Definition for Sn is as follows: Sn =
1.7321 * VT rating * CT rating. The voltage is the line-to-
line voltage.
Only available if: Device Planning: PQS.Mode = Pickup
Pr<
0.003 - 10.000VAn
0.80VAn
[Protection Para
/<1..4>
/Power-Prot
/32[1]]
t
Tripping delay
0.00 - 1100.00s
0.01s
[Protection Para
/<1..4>
/Power-Prot
/32[1]]
States of the Inputs of the Power Protection Module
Name
Description
Assignment via
ExBlo1-I
Module Input State: External Blocking
[Protection Para
/Global Prot Para
/Power-Prot
/32[1]]
ExBlo2-I
Module Input State: External Blocking
[Protection Para
/Global Prot Para
/Power-Prot
/32[1]]
ExBlo TripCmd-I
Module Input State: External Blocking of the Trip Command
[Protection Para
/Global Prot Para
/Power-Prot
/32[1]]